Parts And Accessories

SI5000 Flow monitor

Dimensions

Specifications

Applications
Medium Liquid; Gaseous medium
Medium temperature [ °C ] -25 ... 80
Compressive strength [ bar ] 30
Liquid
Medium temperature [ °C ] -25 ... 80
Gaseous medium
Medium temperature [ °C ] -25 ... 80
Electrical data
Operating voltage [ V ] 19 ... 36 DC
Current consumption [ mA ] < 60
Protection class III
Reverse protection Yes
Boot delay time [ s ] 10
Total input / output
Total number of inputs and outputs Number of digital outputs: 1
Output
Number of outputs 1
Output signal Switch signal
Electrical design PNP
Number of digital outputs 1
Output function Normally open / normally closed; ( parameters can be set )
Maximum switching output DC voltage drop [ V ] 2.5
Continuous current load of switching output DC [ mA ] 250
Short circuit protection Yes
Short circuit protection type Pulse
Overload protection Yes
Measurement / setting range
Probe length L [ mm ] 45
Liquid
Predetermined area [ cm/s ] 3 ... 300
Measuring range at maximum sensitivity [ cm/s ] 3 ... 100
Gaseous medium
Predetermined area [ cm/s ] 200 ... 3000
Measuring range at maximum sensitivity [ cm/s ] 200 ... 800
Accuracy / deviation
Repeatability [ cm/s ] 1 ... 5
Temperature change rate [ cm/s x 1/K ] 0.1; ( Applied to water 5...100 cm/s; 10...70 °C )
Maximum temperature gradient of medium [ K/min ] 300
Switch point accuracy [ cm/s ] ± 2...± 10; ( Applied to water 5...100 cm/s; 25 °C; factory setting )
Hysteresis [ cm/s ] 2 ... 5; ( Applied to water 5...100 cm/s; 25 °C; factory setting )
Reaction time
Reaction time [ s ] 1 ... 10
Liquid
Reaction time [ s ] 1 ... 10
Gaseous medium
Reaction time [ s ] 1 ... 10
Software / programming
Switch point adjustment Button
Working conditions  
Ambient temperature [ °C ] -25 ... 80
Storage temperature [ °C ] -25 ... 100
Enclosure rating IP 67
Certification / testing
EMC electromagnetic compatibility EN 61000-4-2 ESD 4 kV CD / 8 kV AD
EN 61000-4-3RF electromagnetic immunity test 10 V/m
EN 61000-4-4 Burst 2 kV
EN 61000-4-6 High frequency conduction 10 V
Impact resistance DIN IEC 68-2-27 50 g ( 11 ms )
Seismic DIN EN 60068-2-6 20 g ( 55...2000 Hz )
MTTF [ year ] 298
Pressure Equipment Directive Good engineering practice; can be applied to group 2 fluids; fluids of group 1 according to demand
Mechanical technical data
Weight [ g ] 243.5
Size [ mm ] M18 x 1.5
Thread code M18 x 1.5
Material stainless steel ( 1.4404 / 316L ); stainless steel ( 1.4310/301 ); PC; PBT-GF20; EPDM/X
Material ( wet parts ) stainless steel ( 1.4404 / 316L ); O-ring: FKM 80 Shore A
Process connection M18 x 1,5 internal thread
Display / operator
Display Function 10 x LED, Tricolor
Comment
Packing unit 1 piece
Electrical connections
Connector 1 x M12